This page documents the Redfish implementation and its observed hardware behavior. For the BMC user guide, see BMC (Redfish); for the feature rationale and scope, see BMC overview.

SSH and Monitor agent both require the host operating system to be running. SSH needs sshd, while Monitor agent needs a process running on the host. When the host is powered off, hung, or rebooting, both usually report only a connection failure.

A BMC (Baseboard Management Controller) is an independent computer on the motherboard with its own power and network connection. It may still respond when the host’s other services are unavailable, and can provide power state, hardware sensor readings, and hardware events that the operating system cannot provide.

Server Box communicates with the BMC through Redfish’s HTTPS/JSON API. Redfish is a common out-of-band management interface for modern servers.

Redfish IPMI 2.0 over LAN
Transport HTTPS + JSON RMCP+ over UDP 623, binary protocol
Implementation cost in this project dio is sufficient; no native code required No Dart implementation exists; a client would need to be implemented in crates/ behind FFI
Data model Self-describing resources connected by links SDR, SEL, and chassis commands plus vendor-specific raw data
Authentication TLS + session token RAKP
Hardware coverage Generally devices from around 2016 onward Also covers older and entry-level devices
Specification status Actively maintained Last revised in 2013

IPMI’s main advantages are support for older hardware and Serial-over-LAN. This project does not currently include an IPMI client; supporting pre-Redfish hardware would require a separate decision about an FFI client and another security model.

BMC is an out-of-band management channel and an independent side channel in the server configuration. SSH and Monitor HTTP determine where status data and normal operations come from; BMC reads hardware state and performs power operations when the host operating system is unavailable.

BMC is nested in Spi, alongside Wake-on-LAN’s wolCfg:

class Spi {
SshCredential? ssh;
MonitorHttpCredential? monitorHttp;
WakeOnLanCfg? wolCfg;
BmcCfg? bmc; // null when BMC is not configured
}
final class BmcCfg {
String addr; // https://...
String? credId; // BmcCredential shared by several servers
String? certSha256; // pinned after user confirmation
}
class BmcCredential {
String id; // generated ID, not the display name
String name; // unique name shown in the picker
String user;
String? pwd;
}

A BMC account is a separate record referenced by ID. Servers in one rack commonly share an account, so changing it once updates every server that references it. Deleting an account uses ON DELETE SET NULL, so it does not delete the server configurations that used it.

The address and certificate fingerprint belong to one BMC and stay on BmcCfg. Different BMCs may present different certificates; storing the fingerprint on a shared account would verify one device with another device’s fingerprint.

Physical hosts and virtual machines may point to the same BMC. A power operation from any of those records affects the physical host, and PowerState reports the host rather than the guest. The current model does not represent this host/guest relationship; configure BMC only on the physical-host record.

The layers keep the code that can be tested with fixtures independent of real servers:

BmcCfg + BmcCredential user configuration App
↓
RedfishClient TLS trust, sessions, GET/POST package:redfish
RedfishDiscovery one-time resource discovery package:redfish
resources / sensors JSON → models, no IO package:redfish
↓
BmcNotifier state and independent polling App

Only RedfishClient accesses the network. Lower-level parsers receive decoded JSON maps and return models, so vendor differences can be tested against saved responses rather than hardware.

BMCs commonly use self-signed certificates. A BMC has power-control authority, so accepting any certificate at its address could allow another service to impersonate it. Server Box therefore uses a trust-on-first-use flow similar to SSH host-key verification:

  1. The first connection displays the certificate’s SHA-256 fingerprint.
  2. Compare it with the fingerprint shown by the BMC’s own web interface and confirm it.
  3. The App stores the accepted fingerprint and accepts only a matching certificate later.
  4. If the fingerprint changes, the App refuses the connection, shows the old and new values, and asks for verification again.

A BMC may legitimately change its fingerprint after regenerating a certificate or upgrading firmware. A man-in-the-middle attack produces the same symptom, so verify the BMC before accepting a new certificate.

Everything in this section must be discovered from Redfish resources rather than assumed from a vendor name or a common path.

/redfish/v1/ is the fixed entry point, but the IDs below Systems and Chassis are vendor-defined:

Vendor Typical system ID
Supermicro 1
Dell iDRAC System.Embedded.1
OpenBMC system

A client should walk /redfish/v1/Systems, read the collection’s Members, and then access the concrete resources.

Redfish 2020.4 deprecated Chassis/{id}/Thermal and /Power in favor of ThermalSubsystem, PowerSubsystem, and a unified Sensors collection. Many firmware versions still implement only the legacy model; some expose both.

The client should inspect the links actually provided by the Chassis resource, prefer a complete modern model, and fall back to the legacy model when necessary. It should not infer the model from the vendor name.

ResetType advertisements may be unreliable

Section titled “ResetType advertisements may be unreliable”

The ComputerSystem.Reset action advertises supported values through [email protected]. The supported values differ by device; Nmi and PowerCycle may be advertised but unavailable because of firmware behavior or licensing.

The App maps intents such as “restart” and “power cycle” to values advertised by the device and uses a fallback order when needed. If no value can implement an intent, the corresponding button is not shown.

An H3C R5350 G6 advertises ForcePowerCycle, which is not part of the standard Redfish enum, and does not advertise another power-cut operation. Matching only standard names would incorrectly map “power cycle” to ForceRestart.

The candidate list for each intent therefore includes known vendor extensions after the standard names. These extensions come from real device responses and cannot be inferred from the specification alone.

The specification recommends null when a sensor has no reading, but some firmware sends a sentinel instead. For example, the tested H3C device returns 4294967295 (0xFFFFFFFF) for temperatures it cannot read.

The App filters readings by a plausible range rather than matching a fixed list of sentinel values. The current range rejects temperatures below absolute zero or above 1000°C and implausible fan speeds. -1 is retained because it may be a sentinel or a real cold-inlet reading.

Graceful operations only confirm a request

Section titled “Graceful operations only confirm a request”

HPE iLO documents that GracefulShutdown and GracefulRestart depend on the operating system. A 204 No Content response means that the request was accepted, not that the operating system acted on it.

The App polls PowerState until it changes or the timeout expires. The HTTP status code is not treated as the operation’s result.

Redfish sessions are created with POST to SessionService/Sessions, which returns an X-Auth-Token. An undeleted session remains on the BMC until it expires, and BMCs commonly support only a small number of concurrent sessions. Too many leaked sessions can block the management interface.

Each client creates one session and deletes its session resource when disposed. Both normal and failure paths must release the session. Probing the service root does not require a session.

Some Supermicro licenses gate firmware updates and virtual media. Tests indicate that read-only GET requests and ComputerSystem.Reset work without those licenses on some X11 through X13 devices; this is field experience, not a policy for every model.

A 401 or 403 from a sub-resource should be reported as that resource being unavailable and should not fail the entire fetch.

BMC responses are usually slower than operating-system APIs; reading sensors may take several seconds. BMC therefore uses its own polling cycle instead of sharing the normal server-status timer.

Resource IDs, sensor model, and supported reset types are discovery results. Each client discovers them once and caches them; later polls read and convert live values without rediscovering the device structure.

  • Probe GET /redfish/v1/ and its collections
  • Read Systems/{id}: power state, model, serial number, BIOS version, and health rollup
  • Read Chassis/{id}: temperatures, fan speeds, and power draw using the model provided by the device
  • Call ComputerSystem.Reset with a confirmation dialog, negotiated reset type, and polling-based result confirmation

Not included: event logs, storage inventory, boot-device override, virtual media, or relaying access through Monitor agent to BMCs on an isolated management network.

The table below records a device that has actually responded; it is not a compatibility list. Other behavior comes from vendor documentation, recorded responses, and a local test service.

Item Value
Model H3C R5350 G6
BIOS 6.30.50
Redfish version 1.15.1
Root Vendor / Product Both absent; do not rely on them to identify the service
System ID Systems/1
Chassis ID Chassis/1
Sensor model Legacy (Thermal + Power); Sensors is linked but ThermalSubsystem is incomplete, so the legacy model is used
ResetType ForceOff, ForcePowerCycle, ForceRestart, GracefulShutdown, Nmi, On
Temperatures 20 reported; 18 returned the 0xFFFFFFFF sentinel
Fans 8 positions, with two different readings reported for each position
Chassis power 48 W through PowerControl
Sessions One session per connected client, released on close
Certificate Self-signed and valid at test time
Test date 2026-08-23

Not yet covered: Dell (System.Embedded.1), OpenBMC (system), the Supermicro X11–X14 sensor-model transition, HPE iLO graceful operations, and devices that publish multiple systems.

packages/redfish/test/e2e_test.dart is an opt-in, read-only test. It connects to a real device only when these variables are present in the workspace-root .env; otherwise it skips silently:

Terminal window
SBM_E2E_BMC_URL=https://10.0.0.9
SBM_E2E_BMC_USER=...
SBM_E2E_BMC_PWD=...

The test prints discovered resource IDs, sensor model, reset types, and intent mappings. It does not assert that every vendor uses one resource shape. It reads the reset action but never posts to it.

Power control has no automated test. If you verify it manually, use a machine that carries no important workload:

  1. Configure the BMC and verify its certificate fingerprint.
  2. Confirm that the App shows the actual power state.
  3. Press Restart and verify the negotiated ResetType in the confirmation dialog.
  4. Check whether the result is confirmed or accepted. For iLO graceful operations, accepted can be correct; on hardware that distinguishes request from result, it means no state change has been observed and needs investigation.